DC5xD MK3 GENSET CONTROLLER USER MANUAL
34
time
(10.0s)
13
Back to Mains
time
0-3600.0s
(10.0s)
To avoid the switch actions if the mains unstable.If
the remote start signal is invalid (DC5XD MK3 will
check if the mains normal), genset will not switch
immediately, after the delay time, it will transfer to
mains. during the delay, if the remote start signal is
valid, then genset will come into rated running.
14
Back to Gens
time
0-3600.0s
(5.0s)
There shall be loading delay from Mains to Gens if
the remote start signal valid or Mains abnormal
under Cooling time.
15
Cooling time
0-3600.0s
(30.0s)
After unloading, the time of cooling down by radiator
before stop. During the delay, if the remote start
signal is valid, then genset will come into rated
running.
16
Stop idle time
0-3600.0s(5.0s)
Idle-speed running time.
17
E.T.S. hold time
0-600.0s(10.0s)
Stop solenoid on power time.
18
Fail to stop
5-180.0s(30.0s)
If the RPM is 0 during the stop failure time, then the
stop failure time is no needed.
19
Emergency
delay
0-10.0s(1.5s)
Emergency and over frequency alarm delay.
20
Normal alarm
delay
2.0-20.0s(5.0s)
The alarm delay except for emergency stop and
over frequency
21
Normal warning
delay
1.0-20.0s(2.0s)
The warning delay.
22
AC Voltage
abnormal
delay
2.0-
20.0s(10.0s)
Over / under voltage delay.
23
Over current
inverse time
0.1-36.0(36.0)
This option will not take effect until the [27-Over
phase current delay] is set to 0. The overcurrent
delay is inverse time, and the formula is T=t/((IA/IT)
-1)^2.
24
Over power
inverse time
0.1-36.0(36.0)
This option will not take effect until the [28-Over
total power delay] is set to 0. The over power delay
is inverse time, and the formula is T=t/((IA/IT) -1)^2.
25
Transfer switch
delay
0-3600.0s(1.0s)
The time from Mains to Gens.
26
Load / unload
pulse width
1.0-10.0s
(10.0s)
Mains and Gens loading and unloading pulse width,
when it is 10s, it is regarded as continuous output.
27
Over phase
current
delay
0-3600.0s(30s)
When this parameter is set to 0, the over current
delay is the inverse time; if not, the over current
delay is the time set for this parameter.
28
Over total power
delay
0-3600.0s(30s)
When this parameter is set to 0, the over power
delay is the inverse time; if not, the over current
delay is the time set for this parameter.
29
Fuel output
delay
1.0-60.0s(2.0s)
The output time of fuel valve relay before crank.
4)Engine Alarm setting
NO
Parameter
Range
(defaults)
Notes
1
Over speed
0-200%
Rated RPM multiplying by this value is regarded as