DC5xD MK3 GENSET CONTROLLER USER MANUAL
35
over speed alarm value.When the RPM is higher than
the alarm value and comes into over speed delay but
still higher(emergency faults delay), then over speed
alarms. if the value is set as 200, then the over speed
alarm is disabled.
Rated RPM multiplying by this value is regarded as
under speed alarm value.When the RPM is lower than
the alarm value and comes into under speed delay but
still lower (normal faults delay), then under speed
alarms. if the value is set as 0, then the under speed
alarm is disabled.
When the oil pressure is lower than the alarm value
and comes into low oil pressure delay but still lower
(normal faults delay), then low oil pressure alarms. If
the value is set as 0, then the under speed alarm is
disabled.
When the temperature is higher than the alarm value
and comes into high temperature delay but still higher
(normal faults delay), then high temperature alarms. If
the value is set as 200, then the high temperature
alarm is disabled.
When the fuel level is lower than the value and comes
into low fuel level warning delay but still lower (normal
warning delay), then low fuel level warns. If it is higher
than the value then warning clears. If the value is set
as 0, then the low fuel level warning is disabled.
When the fuel level is lower than the alarm value and
comes into low fuel level delay but still lower (normal
faults delay), then low fuel level alarms. if the value is
set as 0, then the under speed alarm is disabled.
Over battery
voltage
warning
Rated battery voltage multiplying by this value is
regarded as over battery voltage warning value.When
the battery input is higher than the warning value and
comes into over battery voltage delay but still higher
(normal faults delay), then over battery voltage warns.
if the value is set as 200, then the over battery voltage
is disabled.
Under battery
voltage
warning
Rated battery voltage multiplying by this value is
regarded as under battery voltage warn value.When
the battery input is lower than the warning value and
comes into under battery voltage delay but still lower
(normal faults delay), then under battery voltage
warns. if the value is set as 0, then the under battery
voltage is disabled.
When the gap between D+ and B+ is over than this
value, and there is charging failure but still high(normal
warning delay), then charge failure warns. Once the
gap is lower than the value, warns clear. If the value is
set as 300, then the charge failure is disabled.
5)Generator alarm parameters