DC5xD MK3 GENSET CONTROLLER USER MANUAL
38
if the voltage is lower than the preset value
under standby status and shutdown after
start and in running status.
23.Mains load: continuous or pulse type
according to time setting. Only for DC52D
MK3.
24.Mains unload: continuous or pulse type
according to time setting. Only for DC52D
MK3.
25.Idle speed control 2: used for speed
controller, there is output under idle but no
output under high speed.
26.Rated running: there is output under rated
running.
5
AUX. INPUT 1
(Functional of PIN
20)
0-40(2.High
temperature
alarm)
0. Disable.
1. Low oil pressure alarm switch.
2. High temperature alarm switch.
3. Low water level warning switch.
4. Low water level alarm switch.
5. Low fuel level warning input.
6. Low fuel level alarm input.
7. Charging failure warning: output when
charging failure.
8. Low oil pressure shutdown disabled:
valid if there is signal input.
9. High temperature shutdown disabled:
valid if there is signal input.
10.External instant warning input.
11.External instant alarm input.
12.Gens un/loading input: connect to the
gens loading switchs auxiliary point.
13.Mains un/loading input: connect to
auxiliary point of mains loading
switch.( Only for DC52D MK3).
14.Shades status input.
15.Auto start disabled: gens will not start if
there is signal input whatever mains normal
or not.
16.Auto stop disabled: gens will not stop if
there is signal input whatever mains normal
or not.
17.Stop by radiator if high temperature:The
controller will shutdown the gens after high
speed cooling down delay when
temperature is too high if this signal is valid
and gens under normal running . the
controller will shutdown the gens directly if
the signal is not valid.
18.Remote start(with load): the gens comes
into start procession if this signal is valid
and under auto mode.
6
AUX. INPUT 2
(Functional of PIN
21)
0-40(1.Low oil
pressure switch)
7
AUX. INPUT 3
(Functional of PIN
22)
0-40(27.Remote
start)
8
AUX. INPUT 4
(Functional of PIN
38)
0-40(8.Low Fuel
level warning
input)
9
AUX. INPUT 5
(Functional of PIN
39)
0-40(6.Low water
level alarm
input)