DC8xD MK3 GENSET CONTROLLER USER MANUAL
20
0RPM
Idle
Rated speed
Pre-
heat
delay
5S
Long-
est
pre-oil
supply
delay
0S
Start
Crank
delay
2S
8S
Safe
time
8S
Start
idle
time
5S
Longest
speed
increasing
time
120S
Idle
Rated speed
Pre-
heat
delay
Longest
temperature
increasing
time
10S
Longest
voltage
built/
increasing
time
120S 10S
rated
runn-
ing
Transfer
back to
mains delay
10S
Cooling
running time
30S
Stop
idle
time
5S
ETS
solen-
oid
hold
10S
Wait
Stop
30S
warming
up time
Crank
test
time
Automatic starting mode:
press and make sure it is in the stop position before starting.
Press and the test file indicator is on. At this time, it is detected whether the
connection of each sensor is normal. If the sensor is open, the sensor opens an
alarm. If it is normal, wait for the remote start signal to be valid (DC82D MK3
detected the remote starting signal is valid or the mains provide the power is invalid).
The unit will perform the starting process in the following sequence. When the unit
enters the normal rated operation, it will automatically switch to the generator provide
the power. The controller will detect the remote start signal and the mains status in
real time (DC82D MK3 is available). When the remote start signal fails and the mains
provide the power returns to normal, the shutdown process after the "loop time delay"
is performed (DC82D MK3 is available).
Auto start and stop process:
Auto
Start
delay
0RPM
Idle
Rated speed
Pre-
heat
delay
5S
5S
Long-
est
pre-oil
supply
delay
0S
Start
Crank
delay
2S
Crank
test
time
8S
Crank
rest
time
10S 8S
Safe
time
8S
Start
idle
time
5S
Longest
speed
increasing
time
120S
Idle
Rated speed
Auto
Start
delay
Pre-
heat
delay
Longest
temperature
increasing
time
10S
Longest
voltage
built/
increasing
time
120S 10S
rated
runn-
ing
Transfer
back to
mains delay
10S
Cooling
running time
30S
Stop
idle
time
5S
ETS
solen-
oid
hold
10S
Wait
Stop
30S
warming
up time
Crank
test
time
Notices in Starting Process
Note 1: During the Cranking time, the controller automatically detects the speed
signal, frequency signal and oil pressure value or the charging voltage (according to
the parameter setting) to reach the judgment condition of successful start, then the
judgment is that the start is successful and the motor relay is closed.
Note 2: Within the safety delay, only respond to emergency stop, immediate
stop, over speed, over frequency, Overvoltage, shutter open abnormal, other alarms
are not responded to.
Note 3: No response to alarm and warning of under speed, low frequency,