DC8xD MK3 GENSET CONTROLLER USER MANUAL
35
LCD light will be closed automatically without any
button pressed after delay. If setting as 200.0s,
back light always lighted.
The time when the page reverts back to the home
page. If setting as 600.0s:disabled.
LOGO delay
display
under standby
Start screen will be opened without any button
pressed after delay. If setting as 6000.0s: disabled.
7)USB/485 PORT
The IP built by controller and PC.
0-4800
1-9600
2-19200
3-38400
4-57600
5-115200
RS485 communication baud rate.
8)Data/time setting
Permanent calendar inside, please correct the date
timely.
Permanent calendar inside, please correct the time
timely.
Permanent calendar inside, please correct the date
timely.
9)Self-define curve
Self-define oil pressure resistance curve
Sensor curve can be User-defined by
panel buttons, resistance and according
value should be input, MAX 15 groups,
MIN 2 groups.
Rule: resistance should be input from
small to large.
Self-define oil pressure voltage curve
Self-define water temperature curve
Self-define fuel level curve
11.Fault finding
Controller no response
with power
Check DC voltage.
Check DC fuse.
Check if the terminal 1 and 2 is with battery voltage.
Check the water/cylinder temperature is too high or not.
Check the genset AC voltage.
Check DC fuse.
Check the emergency stop button.
Check that the voltage of the controller's 3 feet to the ground
should be the battery voltage.
Check the controller connection.