DC8xD MK3 GENSET CONTROLLER USER MANUAL
26
When the controller detects that the frequency is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights will light up and
displays "Stop fail-Hz" on the current fault screen.
Stop failure with pressure alarm
When the controller detects that the Oil Pressure is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights will light up and
displays " Stop fail-OP-A " on the current fault screen.
Stop failure with oil pressure switch
When the controller detects that the oil pressure switch has not returned after the
stop, it will alarm, the public alarm light “ALARM” lights will light up, and the current
fault screen displays “Alarm: Stop fail-OP-D”.
10.Parameter setting
Enter the edition page
Please set the parameters according to below steps:
1) In the stop mode, please and simultaneously, then loose so that
you can come to password interface, the default password is “07623”.
2) Press and add number 1, press to reduce number 1, press to turn
the digit into right, press to turn the digit into left, press once done. Then
system comes into menu after confirmation of password setting. The screen will
display error if password is wrong. The correct password should be put after
pressing any button.
3) Press to turn the digit into upper position, press to turn the digit into
lower position, press to get into parameters setting page.
4) Press to shift up the parameters, press to shift down the parameters,
press to get into parameter changing page.
5) Press to add number 1, press to reduce number 1, press to turn the
digit into right and press to turn the digit into left, press once done. If the
parameters setting is in the valid setting range, then it can be saved, if not, it can’t
be saved.
6) Press and to save the parameters and exit from edition page.
7) Press to revert back to last class if in any setting position.
Revert back to default: put password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can’t be saved if the user didn’t press OK and STOP to confirm
the setting.
Parameter list.
1) Basic setting