EasyManuals Logo
Home>Megger>Test Equipment>AVTMTTR100

Megger AVTMTTR100 User Manual

Megger AVTMTTR100
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
M
AVTMTTR100-ENG Rev 6 Nov 2015
40
Table 5-3. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship
Copyright 2009 Megger
Winding Connection Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding (U1)
Low-Voltage
Winding (U2)
Phase
Tested
Winding
Shorted
By TTR
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn Ratio
Remarks
21
Dzn4
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2W-2N
2U-2N
2V-2N
Neutral
accessible
on zigzag
winding
22
Dz4
U
V
W
1U-1V
1V-1W
1W-1U
2W-2U
2U-2V
2V-2W
No neutral
accessible
on zigzag
winding
23
Dzn6
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2N-2U
2N-2V
2N-2W
Neutral
accessible
on zigzag
winding
24
Dz6
U
V
W
1U-1V
1V-1W
1W-1U
2V-2U
2W-2V
2U-2W
No neutral
accessible
on zigzag
winding
25
Dzn8
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2V-2N
2W-2N
2U-2N
Neutral
accessible
on zigzag
winding
26
Dz8
U
V
W
1U-1V
1V-1W
1W-1U
2V-2W
2W-2U
2U-2V
No neutral
accessible
on zigzag
winding
1.5U1
U2
U1
U2
1.5U1
U2
U1
U2
1.5U1
U2
U1
U2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger AVTMTTR100 and is the answer not in the manual?

Megger AVTMTTR100 Specifications

General IconGeneral
BrandMegger
ModelAVTMTTR100
CategoryTest Equipment
LanguageEnglish

Related product manuals