EasyManua.ls Logo

Megger AVTMTTR100 - Page 57

Megger AVTMTTR100
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SETUP AND CONNECTIONS
AVTMTTR100-ENG Rev 6 Nov 2015
49
Table 5-4. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding (HV)
Low-Voltage
Winding (LV)
Phase
Tested
Winding
Shorted
By TTR
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn
Ratio
Remarks
14
YNy0
A
B
C
B2 - N
C2 - N
A2 - N
A2 - N
B2 - N
C2 - N
a2 - b2
b2 - c2
c2 - a2
HV
LV
No
accessible
neutral on LV
winding
15
Yyn0
A+B
B+C
C+A
A2 - B2
B2 - C2
C2 - A2
a2 - b2
b2 - c2
c2 - a2
HV
LV
No neutral
accessible
on HV
winding
16
Yy0
A+B
B+C
C+A
A2 - B2
B2 - C2
C2 - A2
a2 - b2
b2 - c2
c2 - a2
HV
LV
No neutral
accessible
on HV & LV
windings
17
YNyn6
A
B
C
A2 - N
B2 - N
C2 - N
n - a1
n - b1
n - c1
HV
LV
Neutral
accessible
on HV & LV
windings
18
YNy6
A
B
C
B2 - N
C2 - N
A2 - N
A2 - N
B2 - N
C2 - N
b1- a1
c1- b1
a1- c1
HV
LV
No neutral
accessible
on LV
winding
19
Yyn6
A+B
B+C
C+A
A2 - B2
B2 - C2
C2 - A2
b1 - a1
c1 - b1
a1 - c1
HV
LV
No neutral
accessible
on HV
winding

Table of Contents