4. Technician settings (cont’)
-34 -
P99 – One or Two set points (for cool and for heat) (FC only!)
“00” - One set point for cooling and heating (default)
“01” - two set points – one for cool and one for heat
P100 – Enable/Disable Screen dimming
“00” - Disable
“01” - Enable (default)
P101 – Screen dimming delay
Range: 0...99 minutes
Default: 5 minutes
P102 – Dimming percentage value
Range: 1,5,10...90%
Default: 10%
P105 – Display brightness
Range: 50...100%
Default: 100%
P114 – Cool PID Kp (FC only!)
Range: 0...100%
Default: 100%
P115 – Heat PID Kp (FC only!)
Range: 0...100%
Default: 100%