SYSTEM LOGS: The FD4 has three separate data logs; 1) alarm log, 2) event log, and 3) pressure log. The alarm log is a
subset of the event log and only displays the last ten alarms that have occurred or cleared. The event log records all alarm and
system function type events
SYSTEM LOGS
1) Event Log
2) Pressure Log
SYSTEM LOGS: The [UP] and [DOWN] arrow buttons can be used to scroll through the
three data logs. The [CHANGE/ENTER] button enters and exits the alarm/event details in
either the Alarm or Event logs. In the Pressure Log the [CHANGE/ENTER] button changes
the skip rate used to scroll through the logged pressure readings.
# 1 EVENT LOG
System in Off
Mode Occurred
06/15/10 13:15:15
PRESSURE LOG
06/15/10 17:52:45
112 psi
Skip Rate:[EACH ]
# 1 EVENT DETAILS
System in Off
Mode Occurred
06/15/10 13:15:15
PRESSURE LOG
06/15/10 17:52:30
112 psi
Skip Rate:[EACH ]
# 1 EVENT DETAILS
Pressure: 83.2psi
System Auto:Yes
Engine Running:No
PRESSURE LOG
06/15/10 17:52:15
113 psi
Skip Rate:[EACH ]
# 1 EVENT DETAILS
Charger #1 OK:Yes
Charger #2 OK:Yes
Battery #1 OK:Yes
# 1 EVENT DETAILS
Battery #2 OK:Yes
AC Power Avail:Yes
Low Fuel Level:NO
# 2 EVENT LOG
Engine Failed To
Start Alarm Occurred
06/15/10 07:32:15
# 3 EVENT LOG
AC Power Failure
Alarm Cleared
06/15/10 07:09:48