Page 26 of 34
File Name: Doc#586p.docx
IftheoriginalSDmem orycardisnolongeravail ableablankSDmemorycard(formattedtoFAT)canbeused.
Thefirm ware ofthecontrollerwillcreatethenecessarylogfilesandwillcontinuetooperate.WhenthenewSD
memorycardisinse rtedalloftheeventsand
pressurelogsthatweremissedwillbeautomatic allycopiedfrom
theintern allymemorytothenewSDmemorycard.Asthelogsar ecopyingtotheSDcardtheOIDwilldisplay
thefollowmessage.
PLEASE WAIT....
CAPTURING UNSAVED
EVENT LOGS 13
PRESSURE LOGS 159
Afterthecontrollerhasfinishedcopyingthelogsstore dinternallytotheSD
cardthealarmswi llbecleared.This
operationcantakeafewsec ondsuptomanyminutesdependingonthequantityoflogstocopyandthespeed
oftheSDcard.
2. SDLoggingError
ThecontrollercandetectproblemsloggingtotheSDcard.Ifthereisa
loggingerrorthepanelbehavesinthe
samewayaswhentheSDcardisremoved.TheonlydifferenceisthattheSDcardwillstillbeinthecontrol
panel.Thecontrollerwillperiodicallytrytorecoverfromloggingerrorsandifsuccessfulthealarmsandmessage
onthe
OIDwillclear.However,ifthemessageontheOIDcontinuestodisplayforover15minutestheSDcard
shouldbereplace dwithanewcardortheoldcard canbereformatted toFAT(notFAT32orexF AT)usingaPC.
Itisrecommendedthatanyfilesthatare
readablefromaPCarecopiedbeforethecardisre format ted.
3. Descriptionofthefile sstoredontheSDmemory card
Filename Description
EVENTS.TXT The main log file. Contains a maximum of 3000 events occurred on the controller in date order. After
the 3000 limit is reached the oldest events will be overwritten from the top of the file.
FD4FW.HEX Original firmware, Metron Eledyne use only.
FW_DEF.TXT A file containing the version number of the FD4FW.HEX firmware file. Metron Eledyne use only.
SETTINGS.TXT This file is created when ‘save all settings’ is executed from the controller, contains the saved settings.
SCREENS.NEW Data file used for the screen messages on the OID, Metron Eledyne use only.
MISCTEXT.NEW Data file used for the messages on the OID screens, Metron Eledyne use only.
AUXALM.TXT Obsolete. Replaced by SETTING.TXT but may still be on the SD card.
CONFIG.TXT Configures the LEDs on the OID, Metron Eledyne use only.
PRESS**.TXT Contains the pressure log where ** is the day of month 01 through 31. Each month will overwrite the
previous month’s data day by day. At the start of each matching day number the old file is deleted and
a new file recreated.
TheSDcard maycontainotherfiles.Normallythesewouldbedrawingsorotherdocument sinPD Fform at.See
PartIXab ov eforadesc ript ionoftheformatofthepressureandeventlogfiles.