3. Operation
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer
that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
Check that the RS 232 cable is correctly connected and that the battery circuit breaker
is closed.
"UPS Driver" installation:
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running
Windows.
2 - Open the Windows File manager or Explorer and select the CD-ROM drive.
3 - Double-click "\Emb\Index.htm", then "UPS Driver".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing
a number of tabs, each presenting a set of parameters.
"ON / OFF conditions" tab
Personalizable function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled