EasyManua.ls Logo

MHS Boilers REGENCY 4 MODULEK/169 - Air Supply by Mechanical Ventilation

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Low level 540 cm
2
plus 4.5 cm
2
per
(inlet) kilowatt in excess of 60 kW
total rated input (gross)
The actual minimum effective areas of the air vents required are as follows:
BOILER MODEL POSITION AREA OF VENT
OF AIR VENT (Air direct from outside)
High Level 567 cm
2
per boiler
Regency 4 Modulek-152
Low Level 1133 cm
2
per boiler
High Level 615 cm
2
per boiler
Regency 4 Modulek-169
Low Level 1230 cm
2
per boiler
High level 663 cm
2
per boiler
Regency 4 Modulek-186
Low Level 1326 cm
2
per boiler
High level 709 cm2 per boiler
Regency 4 Modulek-203
Low Level 1418 cm
2
per boiler
High level 757 cm2 per boiler
Regency 4 Modulek-220
Low Level 1514 cm
2
per boiler
High level 808 cm
2
per boiler
Regency 4 Modulek-237
Low Level 1615 cm
2
per boiler
High level 856 cm2 per boiler
Regency 4 Modulek-255
Low Level 1712 cm
2
per boiler
High level 907 cm
2
per boiler
Regency 4 Modulek-272
Low Level 1813 cm
2
per boiler
2.4.2
AIR SUPPLY BY MECHANICAL VENTILATION
Mechanical ventilation systems serving the area containing the boiler should be designed
with an extraction air rate of 0.45 m
3
/sec per 1000 kW total rated input, and an inlet air
rate of 1.1 m
3
/sec per 1000 kW total rated heat input.
Systems employing an extract fan only must not be used, whereas the use of a single inlet
fan, or an inlet together with an extract fan is acceptable.
All air inlet and extract fans should be electrically interlocked to cause safety shut-down
or lock-out of the boiler in the event of malfunction of either fan.
The requirements of mechanical ventilation schemes is fully outlined in BS.6644.

Related product manuals