MF-PFTT
Instruction : mi-261gb_090212
NOTE !
Read the entire instruction carefully before start.
Application
MicaFlex PFTT is a pressure and flow transmitter
with built in PI-controller and a temperature input
which makes it possible to compensate flow mea
-
surement for temperature changes.
MF-PFTT can be programmed to activate a purging
unit, MF-PU-2, for automatic cleaning of flow sen
-
sors with compressed air on set intervals.
With the four key pad, ¹, ¸, PGM and ESC
, the de
-
sired function is selected as well as setting and scal
-
ing is done. The dual row LCD display clearly indi
-
cates the selected function.
Installation
MF-PFTT is designed to be placed on a wall or for
recessed mounting through a wall or cabin door.
When recessed mounting, a mounting kit,
MFM-PANEL is used. The unit is fixed to the wall by
four screws, max 4 mm. The location of the holes is
shown at the back of the enclosure.
Unscrew the four screws of the front cover and use
the bottom screws to attach the front cover on the
upper end of the casing, see Fig 2. This makes in-
stallation and electrical connection easier.
Connect power supply according to the electrical
connection.
To each front cover the CPU is mounted, since the
I/O calibration of the main circuit board is stored on
the CPU-board, it is not possible to move the front
cover between different units.
Output signal
MF-PFTT has two analogue outputs to be used for
actual value of pressure and flow, temperature,
purging unit or PI-control output for pressure or flow.
VDC or mA output signal must be set by the
DIL-switch (DIL1). The same programming must
then also be done under “Outputs”.
Basic programming instruction
When the power supply is connected a start menu
will be displayed. With ¹¸ it is possible to scroll
through the different start menus. To always have
the same start menu, the selection is programmed
under “System settings”. Pressing ESC when some
other menu is displayed returns to the menu pro-
grammed under “Display”.
Programming
Press PGM until "PROGRAM-MENU" appears. Re
-
lease the key and the display shows parameter
group, see table on page 2.
With ¹¸ it is possible to scroll through the parame
-
ter groups.
1. Current values
2. System settings
3. Outputs
4. Pressure
5. Flow
6. Temperature
7. PI2 controller
8. Purging unit
9. Communication
10. Internals
When the parameter group to be programmed is
shown, press PGM. The parameters are then
shown, with ¹¸ select the parameter to be pro
-
grammed and press PGM.
© AB MICATRONE 2009-02-12 [H:\ Apps \ Typeset \ Mima \ Mi-261gb_090212.vp]
Programmable differential pressure transmitter
for pressure or flow measurement and control
with purging function for flow sensors.
®
Operating and installation manual
ON
12345
DIL1
J5
D1
L
3
PL1
N-
L+
Output/Utsignal
N-
Ou
t
Ou
t
2
1
Fig 1
DIL 1: 1 on, 2 off volt output 1
3 on, 4 off volt output 2
1 off, 2 on mA output 1
3 off, 4 on mA output 2
A
A
Fig 2
Use the front cover bottom screws (marked A)tofixthefront
cover at the enclosures top edge during installation.
Question and Answer IconNeed help?

Do you have a question about the Micatrone MF-PFTT and is the answer not in the manual?

Micatrone MF-PFTT Specifications

General IconGeneral
BrandMicatrone
ModelMF-PFTT
CategoryTransmitter
LanguageEnglish

Summary

Product Introduction and Application

Application Details

Explains the MicaFlex PFTT's function as a pressure/flow transmitter with Pl-controller and temperature compensation.

Installation Guide

Provides instructions for mounting the unit on a wall or in a panel, and connecting electrical components.

Device Operation and Programming

Basic Programming Instruction

Outlines how to start the device and navigate basic menus, including setting the default display.

Parameter Groups Overview

Lists all accessible parameter groups for configuration, such as System Settings, Outputs, Pressure, and Flow.

Programming Workflow

Illustrates the interactive process of selecting parameter groups, parameters, and entering values using PGM and ESC keys.

Data Entry and Security Features

Covers digit-by-digit programming, unit/value changes, operation cancellation, and key lock activation.

Output Signal Configuration

Details selecting and scaling analogue outputs for pressure, flow, PI2, or temperature values.

Pressure Measurement Settings

Explains unit selection (Pa, mbar, etc.), range notes, and sign display for differential pressure.

Flow Measurement Configuration

Covers flow unit selection, scaling (Max flow, Scale flw), and temperature compensation settings.

Temperature Sensor Input Setup

Guides on selecting and scaling temperature sensor inputs like analogue signals or Pt-100/Pt-1000 sensors.

PI2 Controller Setup

Details PI2 controller settings: source, mode, output type, set points, neutral zone, and I-time.

Purging Unit Functionality

Explains programming the purging unit for OFF, ON, or TEST modes, including on-time and pause intervals.

Technical Information and Maintenance

Technical Specifications Summary

Presents key technical data including indicator, pressure/flow ranges, accuracy, and power supply requirements.

Electrical Connection Diagrams

Provides wiring diagrams for power, analogue outputs, and temperature sensor inputs, including DIL switch settings.

Maintenance and Zero Setting

Details periodic maintenance, including the procedure for checking and setting the pressure transmitter's zero offset.