15
Information Inquiry
To enter INFORMATION INQUIRY STATUS, hold both ON/OFF and FAN for 8 seconds to activate. To exit the inquiry mode, let the
remote remain idle for 60 seconds.
Table 8 displays the information codes. The screen displays the code for two seconds, then the information for 25 seconds.
Table 8 — Information Codes
EXPLANATION DISPLAYED CODE ADDITIONAL NOTES
T1 T1 T1 temperature
T2 T2 T2 temperature
T3 T3 T3 temperature
T4 T4 T4 temperature
TP TP TP temperature
Targeted frequency FT Targeted Frequency
Actual frequency Fr Actual Frequency
Compressor current dL Actual amperage
Outdoor AC voltage Uo Actual voltage
Indoor capacity test Sn N/A
Reserve -- N/A
Outdoor fan speed Pr Outdoor fan speed=value*8
EXV opening angle Lr EXV opening angle-value*8
Indoor fan speed ir Indoor fan speed=value*8
Indoor humidity HU N/A
Adjusted setting temperature TT Setpoint in Celsius
Reserve -- N/A
Reserve -- N/A
Reserve -- N/A
GA algorithm frequency oT N/A
Reserve LH N/A