26
ERROR 
CODE
MALFUNCTION 
OR PROTECTION
FAILURE CAUSE 
AND CORRECTIVE ACTION
1. Strong wind or typhoon below toward to the fan, to make the 
fan running in the opposite direction. Change the unit direction 
or make shelter to avoid typhoon below to the fan. 
2.fan motor is broken, change a new fan motor. 
The DC fan failure
1. Whether the power supply input is in the available range. 
2. Power off and power on for several times rapidly in short time. 
Remain the unit power off for more than 3 minutes than power 
on. 
3. the circuit defect part of Main control board is defective. 
Replace a new Main PCB.
Main circuit voltage failure
1. Pressure sensor connector is loosen, reconnect it. 
2. Pressure sensor failure. change a new sensor.
Pressure sensor failure
 Refer to P0
Low pressure protection
(Pe<0.6) occured 3 times 
in an hour 
 Refer to H6
H6 displayed 10 times in 2 
hours 
1. The EEprom parameter is error, rewrite the EEprom data. 
2. EEprom chip part is broken, change a new EEprom chip 
part. 
3. Main PCB is broken, change a new PCB.
The main control board PCB 
B EEprom failure
1. System is lack of refrigerant volume. Charge the refrigerant 
in right volume. 
2.When at heating mode or DHW mode, the outdoor heating 
exchanger is dirty or something is block on the surface. Clean 
the outdoor heating exchanger or remove the obstruction. 
3. The water flow is too low in cooling mode.increase the water 
flow.
4. Electrical expansion valve locked or winding connector is 
loosen. Tap-tap the valve body and plug in/ plug off the 
connector for several times to make sure the valve is working 
correctly. 
Low pressure protection