erant if ice blocked.
Check if happened
frequently, if yes, please
replace PCB.
Couldn’t open the EXV.
The EXV, capillary and filter
are dirty, blocked and ice
blocked.
PCB mistakes to alarm.
Inform the customer
service center.
Refrigerant is too less.
Inspect leakage in system,
append refrigerant.
Replace the EXV and coil.
Cause of dirty and blocked,
replace the EXV, capillary and
filter. Vacuuming and append
refrigerant if ice blocked.
Inspect if the water flow is
normal, refer to the water flow
malfunction to analysis.
Couldn’t open the EXV.
The EXV, capillary and filter are
dirty, blocked and ice blocked.
The pressure controller is
broken or joint is loose.
Anti-freezing lower pressure
protection.
Inform the customer service
center.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Replace the pressure controller,
fixed joint.