MCAC-ATSM-201704 Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
38
2) Current protection
3) High temperature protection of condenser
High temperature protection of
condenser.
Yes
Clean heat exchanger.
Check the fan motor,
capacitor (1 phase) or
start up water pump.
Empty, vacuuming and
append refrigerant if
necessary
.
Check power supply,
start up the unit after
normal power supply.
Replace PCB.
Inform the customer service
center.
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Abnormal power supply.
Air is in system, filled too much
refrigerant(Generally happened
after maintenance.)
PCB mistakes to alarm.
Yes
Yes
The fin of heat exchanger is
dirty or aged in cooling mode.
Clean heat exchanger.
Replace PCB.
Replace temperature
sensor.
Check the fan motor,
capacitor (1 phase).
Replace installation
position of unit.
PCB mistakes to alarm.
No
The installation position of unit
results in bad heat transfer of
condenser.
Yes
Yes
Yes
Yes
No
In cooling mode, the fan motor
stop running, reversal and run
slowl
y
.
The temperature sensor of
condenser bring drifting when
collect tem
p
erature.
No
No
No
Inform the customer service
center.
Current protection
The fin of heat exchanger is
dirty or aged in cooling mode,
or the shell-tube scaled
stron
g
.
The fan motor stopped running
in cooling mode, reversal and
run slowly. The water pump
didn’t start up or less water
flow in heating.

Other manuals for Midea MC-SU30-RN1L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MC-SU30-RN1L and is the answer not in the manual?

Midea MC-SU30-RN1L Specifications

General IconGeneral
BrandMidea
ModelMC-SU30-RN1L
CategoryChiller
LanguageEnglish

Related product manuals