Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz) MCAC-ATSM-201704
39
4) Inlet &outlet water temperature difference protection
5) Low ambient temperature starting up protection
6) Low temperature anti-freezing protection of cooling evaporator
Inlet &outlet water temperature
difference protection.
Low temperature anti-freezing
protection of cooling
Inform the customer service
center.
Yes
Replace PCB.
Replace temperature
sensor.
Refer to the water flow
malfunction to analysis.
Yes
Yes
Yes
No
No
No
Water flow is lower.
The outlet water temperature
sensor or inlet water temperature
sensor brought drifting when
collect tem
erature.
PCB mistakes to alarm.
Replace temperature
sensor.
Replace PCB.
Inform the customer service
center.
PCB mistakes to alarm.
Yes
Yes
Yes
Yes
No
No
Water flow is slow.
Yes
Refer to the water flow
malfunction to analysis.
Replace temperature
sensor.
Replace PCB.
Anti-freezing temperature sensor of
cooling evaporator brought drifting
Yes
PCB mistakes to alarm.
Inform the customer service
center.
No
No
No
Low ambient temperature starting
protection in cooling mode.
Yes
Ambient temperature sensor
brought drifting when collect
tem