R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
0.75×3-core with shielding
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temperature protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
Sound level(semi-anechoic)
Operation water temperature
Cooling:5~17 Heating:45~50
Cooling:10~52 Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C (140℉)DB.
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m
2
˚C /kW.