94
14.3  Important information for the used 
         refrigerant
 
This product has the fluorinated gas it is forbidden to release 
to air. 
Refrigerant type: R410A; Volume of GWP: 2088;
GWP=Global Warming Potential
Attention:
Frequency of Refrigerant Leak Checks
1) For equipment that contains fluorinated greenhouse gases in 
    quantities of 5 tonnes of CO
2
 equivalent or more,but of less than 
    50 tonnes of CO
2
 equipment,at least every 12 months, or where 
    a leakage detection system is installed, at least every 24 months.
2) For equipment that contains fluorinated greenhouse gases in 
    quantities of 50 tonnes of CO
2
 equivalent or more,but of less than 
    500 tonnes of CO
2
 equipment,at least every six months, or where
    a leakage detection system is installed, at least every 12 months. 
3) For equipment that contains fluorinated greenhouse gases in 
    quantities of 500 tonnes of CO
2
 equivalent or more,at least every 
    three months, or where a leakage detection system is installed, 
    at least every six months. 
4) This air-conditioning unit is a hermetically sealed equipment that 
    contains fluorinated greenhouse gases.
5) Only certificated person is allowed to do installation, operation 
    and maintenance.
 
Model
Refrigerant/kg tonnes CO
2
 equivalent
2.40 
2.40 
2.40 
3.60 
3.60 
3.60 
5.01 
5.01 
5.01
7.52 
7.52 
7.52 
9kW
10kW
12kW
14kW
5kW
7kW
Factory charge
16kW
3.60 7.52