Maintenance and
Disassembly
Page 69
6. Compressor
WARNING: Recover refrigerant from the refrigerant circuit before remove the compressor.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts,
and 3. Fan assembly) before disassembling compressor.
Procedure Illustration
1) Remove the flange nut of terminal cover
and remove the terminal cover (see CJ_
ODU_INV_019).
2) Disconnect the connectors (see CJ_ODU_
INV_020).
CJ_ODU_INV_019
CJ_ODU_INV_020
Note: This section is for reference only. Actual unit appearance may vary.
Terminal Cover