Oasis Inverter DM12-01.01.10en
46 Service manual
For 18k, 24k models:
Model FD FD1
MO11MU-18HRDN1
60 70
MO11MU-24HRDN1
90 100
10.4.3.5 Evaporator coil temperature protection
----T2> TEH2C, the compressor running frequency decreases to the lower level and runs for 20s.
When the frequency decreases to F2 and the T2 is still over TEH2C for 3 minutes, the compressor
will stop.
----T2<48C or T2 stays in 48C ~ TEH2C for 6 minutes, the frequency will not be limited by T2.
----T2>60C, the compressor will stop and restart when T2<48C.
While TEH2=53C.