DM12-01.01.10en Oasis Inverter
Service manual 49
10.4.8 Sleep function mode
10.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.
10.4.8.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1C (be lower than 30C) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1C (be higher than 17C) every one hour, 2 hours
later the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function
has the priority).
8.4.8.3 Timer setting is available
8.4.8.4 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the
timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing
is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode.
10.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart
module. In case of a sudden power failure, the module memorizes the setting conditions before the
power failure. The unit will resume the previous operation setting (not including swing function)
automatically after 3 minutes when power returns.
If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes
and turn to auto mode as 24C setting temp.
If AC is off before power off and AC is required to start up now, the compressor will have 1 minute
delay when power on. Other conditions, the compressor will have 3 minutes delay when it restarts.
10.4.10 Follow me
1) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on
remote controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But
when the indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer
will not respond. When the unit is running with follow me function, the PCB will control the unit
according to the temperature from follow me signal, and the temperature collection function of room
temperature sensor will be shielded, but the error detective function of room temperature sensor will
be still valid.