Setting
Low
Breeze
Off
17
For 9k,12k models:
44
38
37
34
T2
33
Setting
Low
Breeze
Off
TEL0
Super
Breeze
TEL1
TEL1=24,TEL0=17.
If the compressor stops caused by the room
temperature rising, the indoor fan will be forced
to run 127 seconds with breeze. During this
period, the anti-cold-wind is disabled.
If the machine runs in rating capacity test mode,
the indoor fan will run with rating speed and the
anti-cold-wind function is disabled.
Indoor fan speed can be set as high, medium,
low or auto fan and the anti-cold-wind function
is preferential.
Auto fan action in heating mode:
9.4.3.4 Defrosting mode
Condition of defrosting:
----T4>0℃,
When the units are running, if the following two
items are satisfied, the units start defrosting:
The units run with T3<3℃ for 40 minutes and
T3 keeps lower than TCDI℃ for more than 3
minutes.
The units run with T3<3℃ for 80 minutes and
T3 keeps lower than TCDI+2℃ for more than 3
minutes.
----T4<0℃,
If the 1
st
condition and 2
nd
condition items are
satisfied, then the program judges if T2 has
decreased more than 5 ℃ .When T2 has
decreased more than 5℃, enter the defrosting
mode.
----No matter what value T4 is, if the machine
runs with T3<3℃ for more than 120 minutes
and T3 keeps lower than TCDI+4℃ for more
than 3 minutes, the machine will enter
defrosting mode no matter if T2 drops more
than 5℃ or not.
Condition of ending defrosting:
If any one of the following items is satisfied, the
defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1℃.
----T3 keeps to be higher than TCDE2℃ for 80
seconds.
----The machine has run for 10 minutes in
defrosting mode.
Defrosting action:
For 9k and 12k models: