V6-i VRF 50/60Hz
123
Part
6 - Diagnosis and Troubleshooting
2.23 PP: Compressor discharge insufficient superheat protection
Digital display output 2.23.1
Description 2.23.2
Compressor discharge insufficient superheat protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.23.3
Trigger condition: Discharge gas superheat is 0
o
C for 20 minutes or 5
o
C for 60 minutes.
Recover condition: Discharge gas superheat go back to normal value.
Reset method: Resume automatically.
Possible causes 2.23.4
Temperature sensor not connected properly or has malfunctioned.
Poor temperature sensor heat insulation.
Excess refrigerant.
Discharge pressure too high.
Main PCB damaged.