Appendix A: Specifications
124
Model QAA-5230S-70/ 25 Amplifier w ith 2 split 70V or 25V, 30 Watt Zones
• 70.7Vrms or 25V constant voltage output
• Each 30W output divided into 2 Class “B” 15W lines for split speaker line applications (two lines per zone with
staggered speakers); four fully supervised Class "B" speaker zones
• 30 watts per zone, 15 Watts per split
• Freq. response: ULI bandwidth from 800 to 2800 Hz, ULC bandwidth from 400 to 4000 Hz
• Harmonic Distortion less than 2.5% at 1 KHz
• Current Consumption: standby: 55mA
alarm: 350mA, plus 65mA/Watt Speaker Power
Model QAA-5415-70 Amplifier w ith four 70V, 15 Watt Zones
• 70.7Vrms constant voltage output
• Four fully supervised Class "B" speaker zones, 15 watts per zone
• Freq. response:
ULI bandwidth from 800 to 2800 Hz, ULC bandwidth from 400 to 4000 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption: standby: 55mA
alarm: 350mA, plus 75mA/watt speaker power
Model QAA-5415-25 Amplifier w ith four 25V, 15 Watt Zones
• 25Vrms constant voltage output
• Four fully supervised Class "B" speaker zones
• 15 watts per zone
• Freq. response:
ULI bandwidth from 800 to 2800 Hz, ULC bandwidth from 400 to 4000 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption: standby: 55mA
alarm: 350mA, plus 75mA/watt speaker power
Model QMP-5101N or QMP-5101NV Paging Microphone
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS (for QMP-5101NV) enclosures
• Current Consumption: standby: 3mA
alarm: 7mA
Model QAZT-5348DS and QAZT-5302DS Paging Selector Panel
• Mounts in Mircom BB-1000, BB-5000 and BBX-FXMNS enclosures
• Connects to QMP-5101N to provide 48 and 24 zones of paging control
• Up to one per QMP-5101N or QMP-5101NV
• Current Consumption: standby: 10mA/5mA
alarm: 20mA/15mA
Model QMT-5302N or QMT- 5302NV Master Telephone
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS enclosures
• Current Consumption: standby: 1mA
alarm: 13mA
Model QAZT-5348DS and QAZT-5302DS Telephone Selector Panels
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS enclosures
• Connects to QMT-5302N to provides 48 or 24 firefighters’ telephone zones
• Up to six selector panels per QMT-5302N
• Unlimited handsets allowed per telephone circuit, supports up to 5 handsets active at the same time
• Current Consumption: standby: 10mA/5mA
alarm: 22mA/15mA