Analog Scaling Setup
Channel: alternate between analog input channels
Offset: allows you to enter value if sensor is not at the bottom or top of
measured item
Range: of sensor as described on the instrument name plate, or converted
value appropriate to engineering units. For example, 2.31 feet per PSI results
in a 0–23.1’ range on a 0–10 PSI pressure transducer.
Units: engineering units as desired
Auxiliary Output Voltage:
0, 12, 24 VDC
Make certain all items powered by auxiliary are compatible to this selection
Relay Communication Failure:
De-energize: generally appropriate if pumping into a pressure tank
No change: generally appropriate if tank can spill
See Best Practices for Remote Control Applications document
Battery Test:
Runs a routine that puts battery under load and returns nal voltage. This test
is performed daily and recorded on web portal.
A good battery should result in a V-battery test reading of 12.1–12.4 volts,
assuming it as been installed and properly charged.
Server Connection:
Tech support will advise if it should be changed from default.
Miscellaneous
Language
Temperature (C or F)
Audio
Screen Saver
Congurable Settings NOT Shown on the LCD
Alarm threshold settings must be paged to the RTU.