1501
(U2)
Refrigerant shortage trouble
Abnormal points and detection methods Causes and checkpoints
(1)Abnormalwhenallofthefollowingconditionshavebeensatisedfor
15 consecutive minutes:
1.ThecompressorisoperatinginHEATmode.
2.Dischargesuperheatis80: [144
_
F]ormore.
3.DifferencebetweenTH7andTH3appliestotheformulaof
(TH7−TH3<5:[9
_
F])
4.Thesaturationtemperatureconvertedfromahighpressuresensor
detectsbelow35:[95
_
F].
(2)Abnormalwhenallofthefollowingconditionshavebeensatised:
1.Thecompressorisinoperation.
2.Whencooling,dischargesuperheatis80: [144
_
F]ormore,and
thesaturationtemperatureconvertedfromahighpressuresensoris
over−40:[−40
_
F].
3.Whenheating,dischargesuperheatis90:[162
_
F]ormore.
Defectiveoperationofstopvalve(notfullyopen)
Defective thermistor
Defective outdoor multi controller circuit board
IndoorLEVperformancefailure
Gas leakage or shortage
Defective 63HS
TH3 :Thermistor<Outdoorliquidpipe>
TH7 : Thermistor <Ambient>
LEV :Linearexpansionvalve
63HS:Highpressuresensor
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
Chart 1 of 2
Yes
No
No
No
No
Yes
Yes
Yes
Istheoutdoorstopvalve(ball
valve)fullyopen?
Is there a refrigerant leak?
Is5104displayedwhenrestarted?
Is there any abnormality on
connectors such as a disconnection,
half-disconnection or breakage?
Refer to the diagnosis of check code 5104.
Checkrelevantthermistorwiringsand
connector contacts of the outdoor multi
controller circuit board.
Disconnectthethermistorwiringandcheck
the resistance.
Openthestopvalve(ballvalve)fully.
Repairtherefrigerantleak.
Connecttheconnectorproperly
(Repairorreplaceitincaseofabreakage).
(leaking)
(5104)
(no leaking)
(1501)
Continuetothenextpage
59