Abnormal points and detection methods Causes and checkpoints
AbnormalifTH8detectsatemperatureoutsidethespeciedrangeduring
compressoroperation.
TH8:
Thermistor <Heat sink>
Blocked outdoor fan
Malfunction of outdoor fan motor
Blockedairowpath
Riseofambienttemperature
Characteristic defect of thermistor
Malfunctionofinputcircuitonoutdoorpowercircuitboard
Malfunction of outdoor fan driving circuit
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
Is5110displayedwhenrestart?
4230
(U5)
Heatsinktemperaturetrouble
No
Yes
No
No
Yes
Yes
No
No
Yes
Yes
Is5110displayedwhenrestarted?
Does the fan rotate during
compressoroperation?
Isthereanyobstaclewhich
blocksanairowaroundthe
heat
sink
?
Is there any abnormality such
as a disconnection, looseness or
breakage?
Is the resistance normal?
Refer to the diagnosis of check code 5110.
Refer to the diagnosis of check code 4400.
Replacethethermistor
(Defective thermistor).
Replacetheoutdoorpowercircuitboard
(Defectiveoutdoorpowercircuitboard).
Improvetheairowpath.
Connectthewiring/connectorproperly.
Replaceitincaseofabreakage.
CheckthewiringandconnectorconnectionTH8.
Check the resistance of TH8.
(airpathblocked)
(no obstacle)
TH8temp.-resistancecharacteristic
0 180kΩ
25
50kΩ
50
17kΩ
70
8kΩ
90
4kΩ
70