Check code
6607
(A7)
No ACK error
Chart 4 of 4
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
Yes
Yes
Yes
Yes
No
No
No
No
Is the correct kind of transmission
line used?
Isitoperatinginmultirefrigerant
system?
Is the address information correct?
Doesitoperatenormally?
Whenoperatinginamultirefrigerantsystem(2or
more outdoor units), check if any of the indoor unit
storesnon-existingaddressinformation.
Replacethecontrollerboardwhichthe
displayedaddress/attributebelongsto.
Continuedfromthepreviouspage
Defective outdoor multi controller circuit board
(repeatercircuit)ontheoutdoorunitissuspected.
Replacetheoutdoormulticontrollercircuitboardone
byone,thencheckfornormaloperation.
Delete the unnecessary address using
a manual setting function on the remote
controller
(Onlyforoperatinginasystemwiththe
Fresh Master/Lossnay is connected, or in a
multirefrigerantsystemwithgroupsetting
is set).
Whenoperatinginasinglerefrigerant
system (single indoor unit), the controller of
thedisplayedaddress/attributeisdefective.
Applythecorrectkindoftransmissionline,
thenperformtheprocedure1.
Complete
89
OCH668B

Other manuals for Mitsubishi Electric City Multi PUMY-SP125VKM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric City Multi PUMY-SP125VKM and is the answer not in the manual?

Mitsubishi Electric City Multi PUMY-SP125VKM Specifications

General IconGeneral
SeriesCity Multi
Outdoor Unit ModelPUMY-SP125VKM
Cooling Capacity12.5 kW
Heating Capacity14.0 kW
RefrigerantR410A
Operating Temperature (Cooling)-5 to 46 °C
Indoor Unit CompatibilityCompatible with various City Multi indoor units
Power Supply380-415V, 50Hz, 3-Phase
Operating Temperature (Heating)-15°C to 24°C

Related product manuals