Abnormalpointsanddetectionmethods Causesandcheckpoints
Thepurposeofthecheckcodeistopreventindoorunitfromfreezingor
dewcondensationwhichiscausedwhenarefrigerantkeepsowinginto
the unit in STOP.
Abnormalwhenallofthefollowingconditionsaresatised:
1.ThecompressorisoperatinginCOOLmode.
2.15minuteshavepassedafterthestartupofthecompressor,orthe
changeinthenumberofoperatingindoorunitsismade(includinga
change by turning thermo-ON/OFF).
3.Afterthecondition2aboveissatised,thethermistorofindoorunit
in STOP detects TH22j
[
−5 [23°F]for5consecutiveminutes.
Wrongpipingconnectionbetweenindoorunitand
branchbox
Miswiringbetweenindoorunitandbranchbox
MiswiringofLEVinbranchboxorindoorunit
Malfunction of LEVinbranchboxorindoorunit
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
1503
(P6)
Freezeprotectionofbranchboxorindoorunit
No
Yes
Connectthepipingandwiringtothesame
port.
No
Is there a resistance detected?
ConnecttheLEVwiringtotheintended
portproperly.
DisconnecttheLEVwiringofbranchbox
or indoor unit to check the resistance.
ReplacetheLEVcoil.
Checktheportwhichthepipingand
wiringbetweentheindoorunitand
branchboxisconnected.
Isthepipingandwiringconnected
tothesameport?
ChecktheportwhichtheLEVwiring
ofbranchboxisconnected.
Isthewiringconnectedtothesame
portasthecorrespondingbranch
box?
Yes
No
ReplacetheLEVassyinbranchboxor
the LEV of indoor unit that is not
connectingviabranchbox.
Yes
ConnecttheLEVwiringproperly.
ChecktheLEVwiringofindoorunit
thatisnotconnectingviabranchbox
isconnectedproperly.
Yes
No
62