7 PARAMETER SETTINGS
7.3 Basic Setting
*1 When the parameter is written without the IP address setting (blank), the following address is set.
192.168.3.251
Operational Setting
Set the destination alive check conditions for socket communication.
CC-Link IEF Basic Setting
Set the CC-Link IE Field Network Basic.
■Network Configuration Settings
Set the network configuration.
Double-click <Detailed Setting> of the "Network Configuration Settings".
Item Description Setting range
Timer Settings
for Data
Communication
Change/Set Timer Value Select whether to change timer values from the default.
The timer operates with its default value when "No" is selected.
•No
•Yes
(Default: No)
Destination Alive Check
Start Interval Timer
Set the time interval between the reception of the last message from the
external device and the start of alive check.
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 600 s)
Destination Alive Check
Interval Timer
Set the time interval for performing alive check again when no response is
returned from the external device of alive check target.
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 10 s)
Destination Alive Check
Resend Count
Set the number of times to perform alive check when no response is
returned from the external device of alive check target.
1 to 32767
(Default: 3 Times)
Item Description Setting range
Network Configuration Settings Set the information of the slave station to the master station. Moreover,
configure link scan settings (timeout time and number of retries for slave
station disconnection detection). (Page 32)
Refresh Settings Configure the settings to automatically link refresh RX/RY/RWr/RWw data
to the devices. (Page 36)
Station-based Block Data Assurance Set whether to assure the data in station units when refreshing the link
between the host station and CPU module. This prevents the data that is
read/written for each slave is not separated into the new data and old data.
• Enable
• Disable
(Default: Disable)
Item Description Setting range
[Detect Now] button Connected devices are automatically detected.
[Link Scan Setting] button Configure link scan settings.
Connected Count The total number of connected slave stations is displayed.
No. The station number of the slave station is displayed.
Model Name Module model name is displayed.
When there is no module information, "Module With No Profile Found" is
displayed.
STA# The start station number of the slave station is displayed.
Station Type The station type (master station/slave station) is displayed.