EasyManua.ls Logo

Mitsubishi Electric FX5U - Digital Switch

Mitsubishi Electric FX5U
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 WIRING
6.8 Examples of Wiring for Various Uses
105
6
Digital Switch
When DSW instructions are used
Examples of wiring for capturing values from a 4-digit digital switch to the data register D100 are given below.
For the instructions, refer to MELSEC iQ-F FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
Example of program
Example of wiring
Sink wiring
The example is the wiring for the input/output of the FX5U-32MT/ES.
Source wiring
The example is the wiring for the input/output of the FX5U-32MT/ESS.
DSW
SM400
X010 Y010 D100 K1
X010 X011 X012 X013 X015X014 X016 X017
COM2
Y010 Y011 Y012 Y013
Sink input
FX5U-32MT/ES
1248
10
3
10
2
10
1
10
0
10
3
10
2
10
1
10
0
0.1A 50V
diode is
necessary.
Digital
switch of
BCD
Transistor output (sink)
S/S 0V 24V
X010 X011 X012 X013 X015X014 X016 X017
+V2 Y010 Y011 Y012 Y013
Source input
FX5U-32MT/ESS
1248
10
3
10
2
10
1
10
0
10
3
10
2
10
1
10
0
0.1A 50V
diode is
necessary.
Digital
switch of
BCD
Transistor output (source)
S/S 0V 24V

Table of Contents

Related product manuals