2 SPECIFICATIONS
2.7 Built-in Analog Specifications
25
2
2.7 Built-in Analog Specifications
The analog input/output specifications of the built-in analog function are explained below.
For details on the analog built-in function, refer to MELSEC iQ-F FX5 User's Manual (Analog Control).
Analog input
*1 "Digit" refers to digital values.
Analog output
*1 There is a dead band near 0 V output, which is an area where some analog output values do not reflect digital input values.
*2 External load resistance is set to 2 k when shipped from the factory. Thus, output voltage will increase somewhat if the resistance is
set higher than 2 k. When the resistance is 1 M, output voltage increases maximum 2%.
*3 "Digit" refers to digital values.
Item Specifications
Analog input points 2 points (2 channels)
Analog input Voltage 0 to 10 V DC (input resistance 115.7 k)
Digital output Unsigned 12-bit binary
I/O characteristics, Maximum resolution Digital output value 0 to 4000
Maximum resolution 2.5 mV
Accuracy
(Accuracy in respect to maximum digital
output value)
Ambient temperature
25 5 (77 41)
Within 0.5% (20 digit
*1
)
Ambient temperature
0 to 55 (32 to 131)
Within 1.0% (40 digit
*1
)
Conversion speed 30 s /channels (data refreshed every operation cycle)
Absolute maximum input -0.5 V, +15 V
Insulation method Inside the PLC and the analog input circuit are not insulated. Between input terminals
(channels) is not insulated.
Occupied points 0 points (does not pertain to the max. No. of input/output points of the PLC.)
Terminal block used European-type terminal block
Item Specifications
Analog output points 1 points (1 channels)
Digital input Unsigned 12-bit binary
Analog output Voltage 0 to 10 V DC (external load resistance 2 k to 1 M)
I/O characteristics, Maximum resolution
*1
Digital input value 0 to 4000
Maximum resolution 2.5 mV
Accuracy
*2
(Accuracy in respect to maximum analog
output value)
Ambient temperature
25 5 (77 41)
Within 0.5% (20 digit
*3
)
Ambient temperature
0 to 55 (32 to 131)
Within 1.0% (40 digit
*3
)
Conversion speed 30 s (data refreshed every operation cycle)
Insulation method Inside the PLC and the analog output circuit are not insulated.
Occupied points 0 points (does not pertain to the max. No. of input/output points of the PLC.)
Terminal block used European-type terminal block