2 ANALOG INPUT MODULE, MULTIPLE INPUT MODULE FB
2.3 M+Model_SetLoggingParam
11
2
Error code
Error code
(hexadecimal)
Description Action
100 The target channel is set out of the range.
Set the target channel within the following range.
FX5-4AD: 1 to 4
FX5-8AD: 1 to 8
Review and correct the settings and then execute the FB
again.
102 The module type is set out of the range.
Set the module type to the following values.
FX5-4AD: 0
FX5-8AD: 0
Review and correct the settings and then execute the FB
again.