14
3 ANALOG OUTPUT MODULE FB
3.2 M+FX5-4DA_OperateError
3.2 M+FX5-4DA_OperateError
Name
M+FX5-4DA_OperateError
Overview
Labels
■Input label
■Output label
Item Description
Overview Monitors error codes and resets errors.
Symbol
No. Variable name Name Data type Range Description
(1) i_bEN Execution command Bit ON, OFF ON: The FB is activated.
OFF: The FB is not activated.
(2) i_stModule Module label Structure The setting range
differs depending on
the module label.
Specifies the module label for the analog output
module.
(3) i_bErrReset Error reset request Bit ON, OFF Turn on this label to reset the errors.
Turn off this label after the error reset.
No. Variable name Name Data type Default value Description
(4) o_bENO Execution status Bit OFF ON: The execution command is ON.(Module errors are
being monitored.)
OFF: The execution command is OFF.
(5) o_bOK Normal completion Bit OFF The on state indicates that executing the error reset
instruction has been completed.
(6) o_bUnitErr Module error
outbreak flag
Bit OFF The on state indicates that a module error has
occurred.
(7) o_uUnitErrCode Module error code Word [Unsigned] 0 The error code of an error occurred is stored.
(8) o_bErr Error completion Bit OFF Always OFF
(9) o_uErrId Error code Word [Unsigned] 0 Always 0
(7)
(6)
(5)
M+FX5-4DA_OperateError
(4)
(3)
(2)
(1)
o_uUnitErrCode
o_bUnitErr
o_bOK
o_bENO
UW
B
B
B
B
DUT
B
:
:
:
:
(8)o_bErr B
(9)o_uErrId UW
:
:
:
:
:
i_bErrReset
i_stModule
i_bEN