CHAPTER6 FUNCTIONS
1
2
3
4
5
6
7
8
6.11 Monitor Function
6.11.4 Executional conditioned device test
6 - 49
(4) Operating instructions
(a) Registering executional conditioned device test settings
Select the registration target step number on the program editing screen in GX Developer. Then, select
[Online] [Debug] [Executional conditioned device test] [Register executional conditioned device test].
*1: When a word device which is index-modified or indirectly-specified is set, only "16 bit integer" can be specified.
1) Multiple executional conditioned device test registrations for the same step
number
Multiple executional conditioned device test settings can be registered for one step number.
Note, however, that multiple executional conditioned device test settings with same device name cannot be
registered for the same step number.
If this occurs, the registration data will be overwritten. (Even though the same device is specified, if the
execution timing differs, two settings can be registered for one step: one for "Before executing instruction"
and the other for "After executing instruction".)
Figure 6.41 Screen for registering executional conditioned device test settings
Table6.16 Items on the screen for registering executional conditioned device test settings
No. Item
Settingrange
Forbitdevice Forworddevice
1) Program name Name of a program registered in the CPU module
2) Step No. 0 to (Step number for the END instruction)
3) Device Device listed in (2) in this section
4) Execution timing Before executing instruction / After executing instruction
5) Setting value - (Not specified) Setting range corresponding to each data type
6) DEC / HEX - (Not specified) DEC (decimal) / HEX (hexadecimal)
7)
Data type
*1
- (Not specified)
16 bit integer / 32 bit integer / Real number (single
precision) / Real number (Double precision)
3)
5)
1)
2)
4)
6)
7)
Devices that executional conditioned device test settings
can be registered for the start step of the + instruction.
+ D0 D10 D20