9 - 25
LOADING AND INSTALLATION9.
(b) Use a power supply which generates minimal noise between wires and between
the programmable controller and ground.
If excessive noise is generated, connect an isolating transformer.
(c) When using a power transformer or an isolating transformer to reduce the
voltage from 200VAC to 100VAC, its capacity must be equal to or greater than
the corresponding value shown in the following table.
(d) Separate the programmable controller's power supply line from the lines for I/O
devices and power devices as shown below.
When there is much noise, connect an isolating transformer.
(e) Taking rated current or inrush current into consideration when wiring the power
supply, be sure to connect a breaker or an external fuse that have proper blown
and detection.
When using a single programmable controller, a 10A breaker or an external fuse
are recommended for wiring protection.
(f) Precautions on using the 24VDC output for the A1S62PN power supply module
Power Supply
Module
Transformer
Capacity
A1S61PN
110VA n
n: Indicates the number of power supply modules.
A1S62PN
110VA n
CAUTION
Do not connect multiple power supply modules to one module in parallel.
The power supply modules may be heated, resulting in a fire or failure.
I/O
equipment
Insulation
transformer
Insulation
transformer
Programmable
controller
A
C200V
T1
Main
power supply
Relay
terminal block
power supply
Insulation
Transformer
I/O power supply
I/O equipment
On a control panel
Main circuit
power supply
Main circuit equipment
Programmable
controller