108
Use the thickest possible (max. 2mm
2
) wires for the 100/200VAC and 24VDC power cables. Twist these wires starting at
the connection terminals. Use a solderless terminal for wiring a terminal block. To prevent short-circuit due to loosening
screws, use the solderless terminals with insulation sleeves of 0.8mm or less.
Note that up to two solderless terminals can be connected per terminal block.
Supply power to two redundant power supply modules individually (redundant power supply system).
When two redundant power supply modules (Q64RPN, and Q64RP) are placed together and operated as a redundant
power supply system, it is recommended to use one of them as an AC power input and connect the other to an
uninterruptible power supply to the other.
When the LG and FG terminals are connected, ground the wires.
If not, the programmable controller may become susceptible to noise.
The LG terminal has a half of the input voltage.
Terminal block
Solderless terminals
with insulation sleeves