(a) Connecting the terminal to an external display device
Connecting the LIFE OUT terminal allows indication of the remaining life of the module to an external display,
device such as external LED, by turning it off when the life is one year or less.
When the external display device turned off, the remaining life can be checked by the LIFE LED of the Q61P-D
located in the control panel.
(b) Obtaining the output status into an input module and monitoring it by GOT
Obtaining the LIFE OUT terminal status into an input module allows monitoring of the module remaining life in
a sequence program.
The following indicates how to monitor the remaining life of the power supply module in the sequence program
by using GOT.
1) System configuration
Model name Start XY
Q02HPU -
QX40
0000
H
Control panelExternal LED
LIFE OUT terminal
The LIFE LED turns on in orange
Remaining life is 1 year or less