12. After changing the module, click the "Execution" button.
(The following table lists the communication status with the change-target module while the following
screen is displayed.)
When the initial settings of the intelligent function module have been made by GX Configurator, the set data are written to
the intelligent function module.
13. Click the "Execution" button again to start control.
14. The screen that notifies the operation completion appears.
(The following table lists the communication status with the change-target module while the following
screen is displayed.)
Target module, item
Executed/Not
executed
Input module refresh
Not executed
(Data held)
Output module refresh Not executed
I/O hybrid module
Input refresh
Not executed
(Data held)
Output refresh Not executed
Intelligent function
module
Input refresh Executed
Output refresh Executed
FROM/TO instruction No processing
Instruction using intelligent
function module device
No processing
Intelligent dedicated instruction No processing
Intelligent automatic refresh No processing
Buffer memory batch monitor Executed
Target module, item
Executed/Not
executed
Input module refresh Executed
Output module refresh Executed
I/O hybrid module
Input refresh Executed
Output refresh Executed
Intelligent function
module
Input refresh Executed
Output refresh Executed
FROM/TO instruction Executed
Instruction using intelligent
function module device
Executed
Intelligent dedicated instruction Executed
Intelligent automatic refresh Executed
Buffer memory batch monitor Executed