314
1105
[RAM ERROR]
The CPU memory in the CPU module is faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Take noise reduction measures.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
[RAM ERROR]
The CPU shared memory in the CPU module is
faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Qn(H)
QnPH
QnPRH
QnU
1106
[RAM ERROR]
The program memory was corrupted due to
battery exhaustion.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
•STOP RUN/When an END instruction
executed
Check the battery to see if it is dead or not.
If dead, replace the battery.
Take measures to reduce noise.
Format the program memory, write all files
to the CPU module, and reset the module
to run it again. If the same error code is
displayed again, the cause is a hardware
failure of the CPU module. Please consult
your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
1107
[RAM ERROR]
The work area RAM in the CPU module is faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1108
[RAM ERROR]
The work area RAM in the CPU module is faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
1109
[RAM ERROR]
The work area RAM in the CPU module is faulty.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
1110
[TRK. CIR. ERROR]
A fault was detected by the initial check of the
tracking hardware.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1111
[TRK. CIR. ERROR]
A tracking hardware fault was detected.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
Error
code
Error and cause Corrective action