Appendix 1 Error Codes
Appendix 1.3 List of error codes (1000 to 1999)
1510
[SINGLE PS. DOWN]
The power supply voltage of either of redundant
power supply modules on the redundant base unit
dropped.
Collateral information
Common information: Base No./Power supply
No.
Individual information: -
Diagnostic timing
Always
Check the power supplied to the redundant
power supply modules mounted on the
redundant base unit.
RUN: On
ERR.:On
CPU Status:Continue
Qn(H)
QnPH
QnPRH
QnU
1520
[SINGLE PS. ERROR]
On the redundant base unit, the one damaged
redundant power supply module was detected.
Collateral information
Common information: Base No./Power supply
No.
Individual information: -
Diagnostic timing
Always
The cause is a hardware failure of the
redundant power supply module. Please
consult your local Mitsubishi representative.
RUN: On
ERR.:On
CPU Status:Continue
Qn(H)
QnPH
QnPRH
QnU
1600
[BATTERY ERROR
*2
]
The battery voltage in the CPU module has
dropped below stipulated level.
The lead connector of the CPU module battery
is not connected.
The lead connector of the CPU module battery
is not securely engaged.
Collateral information
Common information: Drive Name
Individual information: -
Diagnostic timing
Always
Change the battery.
Engage the battery connector when a
program memory, standard RAM, or the
back-up power function is used.
Check the lead connector of the CPU
module for looseness. Firmly engage the
connector if it is loose.
RUN: On
ERR.:Off
CPU Status:Continue
QCPU
LCPU
1601
[BATTERY ERROR
*2
]
Voltage of the battery on memory card has
dropped below stipulated level.
Collateral information
Common information: Drive Name
Individual information: -
Diagnostic timing
Always
Change the battery.
RUN: On
ERR.:Off
CPU Status:Continue
Qn(H)
QnPH
QnPRH
QnU (except
QnUDV)
1610
[FLASH ROM ERROR]
The number of writes to flash ROM (standard
ROM and system securement area) exceeds
100,000 times. (Number of writes > 100,000
times)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
When writing to ROM
Change the CPU module.
RUN: On
ERR.:On
CPU Status:Continue
QnU
LCPU
1700
[BUS TIMEOUT ERR.]
An error was detected on the system bus.
Self-diagnosis error of the system bus
Self-diagnosis error of the CPU module
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
1710
[UNIT BUS ERROR]
An error was detected on the system bus.
An error was detected in the connected module.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
Always
Disconnect the extension block.
Do not use the LA1S extension base unit.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU