338
2114
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
2115
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed/STOP RUN
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01
Qn(H)
QnPH
2116
[SP. UNIT ERROR]
An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
Instruction was executed for the A or QnA
module under control of another CPU.
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
2117
[SP. UNIT ERROR]
A CPU module that cannot be specified in the
instruction dedicated to the multiple CPU system
was specified.
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
2118
[SP. UNIT ERROR]
When the online module change setting is set to
be "enabled" in the PLC parameter in a multiple
CPU system, intelligent functi
on module controlled
by other CPU using the FROM
instruction/intelligent function module device
(U\G) is specified.
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
When performing the online module
change in a multiple CPU system, correct
the program so that access will not be
made to the intelligent function module
controlled by the other CPU.
When accessing the intelligent function
module controlled by the other CPU in a
multiple CPU system, set the online
module change setting to be "disabled" by
parameter.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
Qn(H)
QnPH
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU