354
2501
[CAN'T EXE. PRG.]
More than one program files exist although no
program name is entered in the Program tab of
"PLC Parameter".
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Enter the program names in the Program tab
of "PLC Parameter".
Or delete unnecessary programs.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
[CAN'T EXE. PRG.]
• There are three or more program files.
• The program name differs from the program
contents.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
• Delete unnecessary program files.
• Match the program name with the program
contents.
Q00J/Q00/Q01
2502
[CAN'T EXE. PRG.]
The program file is incorrect.
Or the contents of the file are not programs.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Ensure that the program version is ***.QPG
and the file contents are programs.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
[CAN'T EXE. PRG.]
The program file is not the one for the redundant
CPU.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Create a program with GX Developer or PX
Developer specifying the redundant CPU
(Q12PRH/Q25PRH) as the PLC type, and
write it to the CPU module.
QnPRH
2503
[CAN'T EXE. PRG.]
There are no program files at all.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
• Check program configuration.
• Check parameters and program
configuration.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
2504
[CAN'T EXE. PRG.]
Two or more SFC normal programs or control
programs have been designated.
■Co
llateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN/When SFC
program is executed
• Check program configuration.
• Check parameters and program
configuration.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
[CAN'T EXE. PRG.]
There are two or more SFC programs.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Reduce the SFC programs to one. Q00J/Q00/Q01
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU