Appendix 1 Error Codes
Appendix 1.5 List of error codes (3000 to 3999)
3100
[LINK PARA. ERROR]
The number of modules actually mounted is
different from that is set in Network parameter
for MELSECNET/H.
The start I/O number of actually installed
modules is different from that designated in the
network parameter of MELSECNET/H.
Parameter-set data cannot be used.
The network type of MELSECNET/H is
overwritten during power-on. (When changing
the network type, switch RESET to RUN.)
The mode switch of MELSECNET/H module is
outside the range.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Check the network parameters and actual
mounting status, and if they differ, make
them matched. If any of the network
parameters is corrected, write it to the CPU
module.
Check the set number of extension base
units.
Check the connection status of the
extension base units and extension cables.
Check the connection of the GOT if it is
bus-connected to the main base unit or
extension base unit.
Set the mode switch of MELSECNET/H
module within the range.
If an error occurs even after taking the above
measures, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
[LINK PARA. ERROR]
A CC-Link IE module with a version that does not
support items set in the network parameter is
mounted/connected.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value,
and correct them as necessary.
Mount/connect a CC-Link IE module with a
version that supports items set in the
network parameter.
QnU
LCPU
3101
[LINK PARA. ERROR]
The link refresh range exceeded the file register
capacity.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
When an END instruction or a COM instruction
executed
Change the file register file for the one that
the entire target range can be refreshed.
Increase the capacity of the file register, or
reduce the link refresh range.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
[LINK PARA. ERROR]
When the station number of the MELSECNET/H
module is 0, the PLC-to-PLC network parameter
has been set.
When the station number of the MELSECNET/H
module is other than 0, the remote master
parameter setting has been made.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Co
rrect the type or station number of the
MELSECNET/H module in the network
parameter to meet the used system.
Qn(H)
QnPH
QnPRH
QnU
[LINK PARA. ERROR]
The refresh parameter for the CC-Link IE module
is outside the range.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Set the refresh parameter within the range of
device setting.
Qn(H)
QnPH
QnPRH
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU