369
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.5 List of error codes (3000 to 3999)
3104
[LINK PARA. ERROR]
The Ethernet, MELSECNET/H and
MELSECNET/10 use the same network
number.
The network number, station number or group
number set in the network parameter is out of
range.
The specified I/O number is outside the range of
the used CPU module.
The Ethernet parameter settings are incorrect.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct and write the network parameters.
If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
[LINK PARA. ERROR]
The network number, station number or group
number of the Ethernet module set in the
network parameter is out of range.
The start I/O number of the Ethernet module set
in the network parameter is out of range.
The Ethernet parameter settings are incorrect.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
LCPU
3105
[LINK PARA. ERROR]
In a multiple CPU system, the CC-Link module
under control of another station is specified as the
start I/O number of the CC-Link network
parameter.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Delete the CC-Link network parameter of
the CC-Link module under control of
another station.
Change the setting to the start I/O number
of the CC-Link module under control of the
host station.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
[LINK PARA. ERROR]
Although one or more CC-Link modules were
configured in "Network Parameter", no CC-Link
modules are installed in the system. The start
I/O number in the common parameters is
different from that of the actually mounted
module.
The station type of the CC-Link module count
setting parameters is different from that of the
actually mounted station.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Correct and write the network parameters.
If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
L02SCPU
L02SCPU-P
L02CPU
L02CPU-P
L06CPU
L06CPU-P
L26CPU
L26CPU-P
[LINK PARA. ERROR]
Although two or more CC-Link modules were
configured in "Network Parameter", only one
CC-Link modules are installed in the system.
The start I/O number of the common parameter
specified in "Network Parameter" does not
correspond to the system.
The station type specified in the Network
Parameter dialog box for CC-Link does not
correspond to the system.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
L26CPU-BT
L26CPU-PBT
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents