374
*1 The parameter No. will be the number obtained by the formula: "start I/O number of the intelligent function module set in
parameter using GX Configurator" 10
H
.
*2 The diagnostic timing of CPU modules other than the Universal model QCPU and LCPU is only when the status of the
CPU module is switched from STOP to RUN.
3401
[REMOTE PASS. ERR.]
Any of the following modules is not mounted in the
slot specified by the start I/O number of the remote
password target module.
• Serial communication module whose function
version B or later
• Ethernet module whose function version B or
later
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Mount the following modules in the slot
specified by the start I/O number of the
remote password target module.
• Serial communication module whose
function version B or later
• Ethernet module whose function version B
or later
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
[REMOTE PASS. ERR.]
Serial communication module or Ethernet module
of function version B or later controlled by another
CPU was specified in a multiple CPU system.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
• Change it for the Ethernet module of
function version B or later connected by the
host CPU.
• Delete the remote password setting.
Qn(H)
QnPH
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU