EasyManua.ls Logo

Mitsubishi Electric Q13UDVCPU - Page 381

Mitsubishi Electric Q13UDVCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
379
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.6 List of error codes (4000 to 4999)
4102
[OPERATION ERROR]
In a multiple CPU system, the link direct device
(J\) was specified for the network module
under control of another station.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Delete from the program the link direct
device which specifies the network module
under control of another CPU.
Using the link direct device, specify the
network module controlled by the own
station.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Q00/Q01
Qn(H)
QnPH
QnU
[OPERATION ERROR]
The module No./network No. /station No.
specified for the dedicated instruction is wrong.
The link direct device (J\) setting is
incorrect.
The module No./network No./number of
character strings exceeds the range that can be
specified.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
QCPU
LCPU
[OPERATION ERROR]
The character string (" ") specified by a dedicated
instruction cannot be used for the character string.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
QnU
LCPU
4103
[OPERATION ERROR]
The configuration of the PID dedicated instruction
is incorrect.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Q00J/Q00/Q01
Qn(H)
QnPRH
QnU
LCPU
4105
[OPERATION ERROR]
PLOADP/PUNLOADP/PSWAPP instructions were
executed while setting program memory check.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Delete the setting for the program memory
check.
When using the program memory check,
delete PLOADP/PUNLOADP/PSWAPP
instructions.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
QnPH
4107
[OPERATION ERROR]
33 or more multiple CPU dedicated instructions
were executed from one CPU module.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Using the multiple CPU dedicated instruction
completion bit, provide interlocks to prevent
one CPU module from executing 33 or more
multiple CPU dedicated instructions.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Q00/Q01
Qn(H)
QnPH
Q00UCPU
Q01UCPU
Q02UCPU
QnUDV
4109
[OPERATION ERROR]
With high speed interrupt setting PR, PRC,
UDCNT1, UDCNT2, PLSY or PWM instruction is
executed.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Delete the high-speed interrupt setting.
When using high-speed interrupt, delete the
PR, PRC, UDCNT1, UDCNT2, PLSY and
PWM instructions.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
*2
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents